RN Turbine Flowmeter

RN Turbine Flowmeter

Corrosion resistant 
Robust stainless steel construction
Very low maintenance and down time 
Withstands high temperature and pressure 
Highly accurate measurement of flow 
Well proven 
Improve product quality 
Reduce waste and costs 
Approvals for use in hazardous areas 
Individual calibration certificates 
Low pressure drop 
Bi-directional flow capability
 
Application 
This range of flowmeters is used for liquids such as water, light oils, solvents and low viscosity chemicals. You can use them for batching, flow rate monitoring, controlling, blending and filling. The flowmeter is highly accurate and often used for testing the performance of pumps, engines, valves and other flowmeters. 
In hazardous areas you can use the flowmeters with the Apollo IS pick-off coil approved to ATEX II I G EEx ia IIC T5. The signal can be used in the IS area or transmitted to the safe area using the intrinsically safe P5 preamplifier and suitable barriers.
 
Instrumentation 
The signal can be used for a local display, remote display or converted for transmission to a separate control system. Apollo have a range of instruments to suit all your requirements.
 
Principle of Operation 
When liquid flows and the rotor turns, the sensor detects the movement of the blade tips and generates pulses. The frequency of the pulses is proportional to the flowrate.
 
Construction
The stainless steel construction is durable and gives excellent corrosion resistance. The rotor is machined from solid making it virtually indestructible. The sleeve bearings provide you with highly reliable performance over long periods.
 
Calibration 
All Apollo RN turbine flowmeters are individually calibrated with water and are traceable to national standards. 
We provide you with a test certificate for each meter showing the number of pulses per litre, which is used to set the instrumentation.
 
Installation 
The flowmeter is installed directly into the pipeline. 
To reduce turbulence and get the best results from your flowmeter we recommend that you install it in a straight section of pipe with at least 10 pipe diameters upstream and 5 pipe diameters downstream. Control valves should be installed downstream of the flowmeter. To prevent foreign particles blocking your line we recommend you install a filter before the flowmeter. 
Preamplifiers are only needed if you have very long transmission distances or an electrically noisy environment close to pumps, motors, generators, switchgear or heavy current carrying cables. 
Intrinsically safe systems always require an IS pick-off coil. The IS P5 preamplifier is required for transmission to a safe area through barriers.